List of Eligible Technologies

Thermal Insulation
Eligible Sub-technologies
Rockwool and glasswool
XPS
EPS
Sprey Polyurethane Foam
Glass Foam
Ceramic Wool
Aerated concrete panel
Polyethylene foam
Minimum performance requirement
Uwall or Uroof < 0.50 W/M2
Referance & Comments
Min 6 cm thickness of the material
ESR (%)
30%
Additional requirement and Additional Requirements for buildings industires
eligible windows
Eligible Sub-technologies
Low-voltage three-phase motors type
Variable Speed Drives (VSD)&Variable Frequency Drives(VRF)&VVVF Drives
Minimum performance requirement
Low Voltage motors : Min IEC 2 class and VSD/VFD/VVVF equipped
Reference&Comments
ECO Design requirements for electrical motors
ESR (%)
Low Voltage motors : 20%
Variable Speed Drives : 20%
Eligible Sub-technologies
Centrifugal type fans
Axial type fans
Minimum performance requirement
Min IEC 2 class electrical motor and VSD/VFD/VVVF equipped
Reference&Comments
ECO Design requirements for electrical motors
ESR (%)
25%
Eligible Sub-technologies
Water Circulation pumps
Submersible pumps
Minimum performance requirement
Min IEC 2 class electrical motor and VSD/VFD/VVVF equipped
Reference&Comments
ECO Design requirements for electrical motors
ESR (%)
25%

Motor Systems

Renewable Energy
Eligible Sub-technologies
Crytalline panels
Thin film panels
Minimum performance requirement
Panel Efficiency > 15% CE mark Certificates or equivalent IEC 61215,
IEC 61730
ESR (%)
100%
Additional requirement for existing buildings and for Industries
Energy Audit + Compliance certification with the standards
Eligible Sub-technologies
Flat Pannels or Vacuum Tube Types
Minimum performance requirement
Conversion efficiency > 75%
ESR (%)
100%
Additional requirement for existing buildings and for industries
Hot water distribution pipeline must be insulated properly
Minimum performance requirement
Seasonal Space Heating Efficiency > 85%
ESR compare to baseline (%)
100%
Additional requirement for existing buildings and industries
Distribution system insulation
Hot water distribution pipeline must be insulated properly

Lighting
Eligible Sub-technologies
LEDs
Others
Minimum performance requirement
Luminaire Efficacy Rating >75 and third party certification like CE, RoHS, VDE, UL or equivalent
ESR compare to baseline (%)
25%
Eligible Sub-technologies
Lighting control and automation systems
Minimum performance requirement
Occupation Controls, Daylight dimming, Timer Controls
ESR (%)
Min 30%
Additional requirement for existing buildings and for industries
Eligible Lighting systems

Monitoring and Control System
Eligible Sub-technologies
Custom Process Automation
Software for remote monitoring and control
Hardware including sensors and analyzors
ESR (%)
20%
Eligible Sub-technologies
Ground source heat pumps
Water source heat pumps
Air source heat pumps
Minimum performance requirement
SEER >5.10 or SCOP >3.40
Referance&Comments
EU Labelling directive for air conditioners – Min A class
ESR (%)
40%
Additional requirement For existing buildings and for industries
Distribution System Insulation
Hot/Cold water distribution pipeline must be insulated properly
Eligible Sub-technologies
Mono And Multi Split Units
Minimum performance requirement
SEER >5.10 or SCOP >3.40
Referance&Comments
EU Labelling directive for air conditioners – Min A class
ESR (%)
40%
Eligible Sub-technologies
Package Air or Water Cooled Chillers
Minimum performance requirement
SEER >5.10 or SCOP >3.40
Referance&Comments
EU Labelling directive for air conditioners – Min A class
ESR (%)
30%
Additional requirement for existing buildings and for industries
Distribution system insulation
Hot/Cold water distribution pipeline must be insulated properly
Eligible Sub-technologies
Mechanical Building Ventilation – Air Handling Units
Minimum performance requirement
– All Fans should have multispeed control
– All bidirectional AHUs have to be equipped with heat exchangers
– min thermal efficiency > 63%
– SEC < 0.40 Wh/m3
Referance&Comments
EU Ecodesign Requirements for NON residential ventilation units
ESR (%)
20%
Additional requirement for existing buildings and for industries
Distribution system insulation
Hot/Cold water distribution pipeline must be insulated properly
Eligible Sub-technologies
Boilers
Burners
Heat Exchangers
Minimum performance requirement
Boilers : Seasonal Space Heating Efficiency > 85% for hot water boiler; Boiler efficiency >85% at 100% load for steam boilers
Burners : Modulation burners only
Referance&Comments
Eco Design requirement for gas and oil fired boilers
ESR (%)
Boilers : 20%
Burners : 20%
Heat Exchangers : 100%
Additional requirement for existing buildings and for industries
Boilers : Distribution system insulation
Hot/Cold water distribution pipeline must be insulated properly

Heating, Cooling and
Ventilation Systems (HVAC)
Eligible Sub-technologies
Screw air compressor
Centrifugal air compressor
Reciprocating air compressor
Minimum performance requirement
– Direct Drive
– Must be equipped with Variable Speed Drivers
– Specific Energy Consumption<100 Wh/Nm3 (5 bar);
150 Wh/Nm3 (10 bar);
180 Wh/Nm3 (15 bar)
Referance&Comments
Working file of EU – Possible requirements for compressor for standard air applications
ESR compare to baseline (%)
20%
Additional requirement for existing buildings and for Industries
Distribution system leakages must be investigated

Compressed Air System